KOC-E-004 Part-5
Transcript of KOC-E-004 Part-5
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 1/19
E.l.J)
c.r_éll
-hJii
aJr-l
KUWAIT
OrL
COMPANY
K.S.C.)
STANDARDS
PUBLICATTON
KOC RECOMMENDED
PRACTTCE
FOR
SELECTIONO
INSTALLATION
AND
MAINTENAI\CE
OF
ELECTRICAL
EQUIPMENT
IN
HAZARDOUS
AREAS
NON-SPARKING
TYPE Ex
?n)
DOC
NO:
KOC-E-004
Part
5
STANDARDS TEAM
W
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 2/19
(fJ.l.J)
c.¿;l3ll
-hJi¡
eS-r
KtIWArr
OIL
COMPANY
(K.S.C.)
STANDARDS
PUBLICATION
KOC
RECOMMEI\{DED
PRACTICE
F OR
SELECTION,
INSTALLATION
AI\D
MAINTENANCE
OF
ELECTRICAL
EQUIPMENT
IN
HAZARDOUS
AREAS
NON-SPARKING
TYPE
Ex n)
DOC
NO:
KOC-E-004
Part
5
ISSUING
AUTHORITY:
I
R
/
STANDARDS
TEAM
DOC.
NO.
KOC-E-OO4
Pt. 5
Page
1
of
18
REV.
2
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 3/19
20/01/96
2
Dr. M.
llyas
ssued
as KOC
Recommended
Practice
\
Amended
Cl.
7.5
1106/2008
ffi@
. Unn¡krlshnan
ask Force
(TF-EE/08)
KOC
RECOMMENDED
PRACTICE
FOR
SELECTION,
INSTALLATION
AND MAINTENANCE
OF ELECTRICAL
EQUIPMENT
IN HAZARDOUS AREAS
NON-SPARKING
TYPE
Ex n
DOC
l\O. KOC-E-004
Part 5
REV.
2
age2
of
18
OC.
NO.
KOC-E-004
Pt.
5
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 4/19
2
Þ
Ë
TABLE
OF
CONTENTS
PAGE
NO.
1.
2.
3.
4.
5.
6.
7.
8.
9.
scoPE
4
APPL'CATION
4
TERIIIINOLOGY
5
REFERENCE
CODES
AND
STANDARDS
6
ENVIRONMENTAL
CONDITIONS
8
SERVTCE
CONDIT]ONS
I
CONSTRUCTIONAL
REQUIREMENTS
8
INSTALLATION
REQUIREMENTS
11
INSPECTION,
MAINTENANCE
AND
TESTING
I3
QUALIW
ASSURANCE
14
MARKING
14
DOCUÍTIENTATION
l5
SPARE
PARTS
fIiAINTENANCE
DATA
16
APFENDIX
-
A
INSPECTION
SCHEDULE
FOR
Ex'N'
or
EEx'n'
17
10.
11.
12.
13.
14.
DOC.
NO.
KOC-E-OO4
Pr. 5
Page 3
of
18
REV,
2
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 5/19
IttE
1.0
scoPE
1.1
1.2
This
part
of
the Recommended
Practice
describes
the
specific
requiremenùs
for
construction,
assessment,
testing
and marking
of
rotating
electrical
machines
with type'n'
protection.
It
also
gives
the requirements
for
fixed
luminaries with type
'n'
protection.
2.O
APPLICATION
2.1
All
equipment
with
type 'n'
protection
whether
rotating
or fixed
are
useful
for Zone
2
only
and
these shall
conform to the requirement
of
this document.
2.2 This
Recommended
Practice
(RP)
covers
those
items of equipment
identified
as
Ex'n' including
all
categories
Ex'nA',
Ex'nC'and
Ex'nR',
The
British
Standards
use Ex'N'and
the
European
Norms
use
Ex'n'.
The
equipment
identified
with
small or
capital
letter
('n N')
and
with
additional
letter'E'
or'e'
are
equally
regarded-
2.3
This
document
is issued
in
the following
six
parts:
ParLl
Recommended
Practice
for
Selection,
lnstallation
and
Maintenance
of
Eleotrical
Equipment
in
Hazardous
Areas:
General Requirements.
Parl2
Recommended
Practice
for
Selection,
lnstallation
and
Maintenance
of
Electrical
Equiprnent
in
Hazardous
Areas:
Flameproof
Enclosure
rd'.
Part
3
Recommended
Practice
for Selection,
lnstallation
and
Maintenance
of
Electrical
Eguipment
in Hazardous
Areas:
lntrinsic
Safety'f.
Parl4
Recommended
Practice
for
Selection,
lnstallation
and
of
Electrical
Equipment
in
Hazardous
Areas:
lncreased
safety'e'
Part
5
Recommended
Practlce
for
gelectlon,
lnstallatlon
and
ilalntenance
of
Electrical
Egutpment
Ín
Hazardous
Areas:
Non'
sparking
tYPe
h'
egulPment-
Part
6
neãommended
Practice
for
Selection,
lnsta
of
Electrical
Equipment
in
Hazardous Areas:
Maintenance
tot
DOC.
NO.
KOC-E-OO4
Pr.
5
REV.
2
age 4
of
18
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 6/19
3.0
TERM¡NOLOGY
3.1
Type
of
Protection
n
A
type
of
protection
applied
to
electrical
apparatus
such
that, in normal
operation,
it is
not
capable
of
igniting
a surrounding
explosive
gas
atmosphere
and
a
fault
capable
of causing
ignition
is
not likely to
occur.
3.2
NormalOperatioll
Electrical
apparatus
with
type of
protection
n
is
in normal operation
when
it
conforms
electrically
and mechanically
with
its
design
specification
and is
used
within
the limits specified
by the
manufacturer.
3.3
Enclosure
All
the
walls of external
casing
that
surround
the
live
parts
of
electrical
apparatus
including
doors,
covers,
cable
entries,
rods,
spindles
and
shafts.
3.4
3.5
Restricted
Breathlng
Enclosure
An
enclosure
that
is
designed
to
restrict
the entry
of
gases
and
vapours.
Enclosed
Bfeak
Device
A
device
that
incorporates electrical contacts
that
are
made and
broken,
and
that
will withstand
an internal
explosion
of flammable
gas
or
vapour
for
which
¡t
is
designed
without
suffering
damage
and
without
communicating
the
internal
explosion
to
the
corresponding
external
flammable
gas
orvapour.
3.6
Non-lncendive
Compon.ent
A
component,
other
than
an
making
and
breaking
a
Pote
enclosed-break
device
with
contacts
for
ntially
ince
ndive
circuit
where
e
ither
the
contacts,
or
the
contacti
ng
mechanism
or the
enclosure
n which
the
contacts are
housed
a
re so
constructed
that
the
component
igniti
on
of
the
prescribed
flamma
ble
gas
or
vapour
u
nde
r
spec
if¡
operating
conditions.
3.7
Sealed
Device
A
device
that
is
so
constructed
that
it
cannot
be
opened
during
normal
service
and
is
sealed
against
entry
of an
external
atmosphere.
3.8
Hermetlcally
SealeÛDevices
A
device
that
is so constructed
that
the
external
atmosphere
cannot
gain
âccess
to
the
interior
and
in
which
any
seal is
DOC.
NO.
KOC-E-OO4
ft. 5
REV.
2
age
5
of
18
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 7/19
3.9
Enerqv
Limited Apparatus
and Circuits
Electrical
apparatus and
circuits
in
which
no
arc,
spark
or thermal
effect
is
capable
of
causing ignition
under
the
test
conditions
prescribed.
3.10 Stopping
Fox
A
device
to
restrict
the flow of a
gas
or liquid
between apparatus
and
a
conduit.
3.11
Creepage
distance
The
shortest distance
between
two
conductive
parts
along
the
surface
of an
electricalinsulating
material.
3.12
Glearance
The
shortest
distance through
the
air
between two
bare
conducting
parts.
3.13
MaximumSurfaceTempefature
The
highest
temperature attained
under
practical
conditions
of
operation
withÍn
the
rating
of apparatus
by any
part
of
any
surface
exposed
to
an
explosive atmosphere
that
may
involve
a
risk.
4.0
REFERENCE
CODES
AND
STANDARDS
4.1
ln the event
of conflict between
this Recommended
Practice
(RP)
and
the
Codes referenced
herein,
the
most
stringent
requirement
shall
apply,
unless
otherwise
specified.
Any
exceptions
or deviations
from
this
document,
along
with
their
mel¡ts
and
justifications,
shall
be
brought
to the attention
of KOC
Controlling
Department
for
their
review,
consideration
and
amendment by Standards
Team
(if
required).
4.3
A
list
of Codes
and
Standards
is
given
below
which
are
this
Recommended
Practice.
However,
the list
does
not
the
use
of
other
technical
source
of
information
provided
that
do notconflictwith
the listed
Standards.
4.4
coDEs,
STANDARQS
.
BS5000Part16
British
Standard specification
for
rotating
el
of
particular
type
or
for
particular
applications
protection N .
4.2
REV.
2
age
6
of
18
OC.
NO.
KOC-E-OO4
ft. 5
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 8/19
þ
\\\
,Í
o
lnstallation
and
maintenance
requirements
for electrical
apparatus with type
of
protection'N'.
.
856941
Electrical
apparatusfor
explosive
atmospheres
with
type
of
protection'N'.
BSEN
60400
Specification
for
lampholders
for
tubular
fluorescent
lamps
and
starter
holders.
B EN
60529
Specification
for
Degrees
of
protection
provided
by enclosures
(lP
code).
tEc
79-15
Electrical
apparatus
for
explosive
gas
atmospheres
with
the
type
of
protection'n'.
a
a
a
a
a
a
a
a
BS
5345 Part
7
KOC-E-004
PBrll
&.2
KOC
Recommended
Practice
for
selection,
installation
and
rnaintenance
of
electrical
equipment
in
Hazardous
Areas.
(General Requirements)
and
(Flameproof
enclosure'd').
KOC-G-0q2
KOC
Standard
for
Hazardous
Area
Classification.
KOC-G-004
KOC
Standard
for
Packing,
Marking
and
Documentation.
KOC-G-0o7
KOC
Standardfor
Basic
Design
Data.
.
KO-C-G-009
KOC
Standard
for
SPare
Parts
and
DOC.
NO.
KOC-E-Oo4
Pr.
5
REV. 2
ageT
of
18
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 9/19
2
,Í
o
Ct
e
R
5.0
ENVIRONMEI{TALCONDITIONS
5.1
The
environment
of
Kuwait,
is
severe
on
all equ¡pment
and must
be
considered
carefully
before procurement of plant
and
equipment.
lt
must
be assumed
that,
unless
otherwise
specified,
equipment
may
be
subjected
to sand
and
fine
particle
dust storms,
salt
laden
winds,
thunderstorms,
heavy
rains,
chemical
contaminants
and
extreme
temperatures.
5.2
KOC
Standard
for Basic
Design
Data,
KOC-G-007,
provides
the
detailed
design
information
regarding
the environmental,
site,
and
utility
supply
conditions
prevailing
throughoutthe
KOC
facilities.
6.0
SERVTCE
CONDlflgNq
6.1
All
materials
used
for
electrical
installation
shall
be
new
and
in all
respects
suitable
for continuous
operation
under
the
environmental
conditions.
6.2
Reliability
of
all
equipment
to
perform continuously
in
the
service
conditions
specified
is
essential.
Such
reliability
of
all components
shall
be substantiated
by
a
similar
component
in
operational
use
elsewhere
for
a
minimum
period
of
3
years.
6.9
All
constructional
material
shall
be of
high
quality
and
as
specified.
prototype or
unproven equipment not having
well established record
of satisfactory
service
shall
not
be
considered.
çONsTRUcTloN¿\L
REOUTREMENTS
7.1
Electrical
apparatus
with
the
type
of
protection
n
is
suítable
for use
in
Zone
2
onlY.
7.0
7.2
Eq
uipment
for use
n
Tone
2 sh
al
be sel
ected
n accordance
w¡th
th
e
criteria
of area
and temperature
classification
s
Part¡
cular
attention
shal
be
g
iven
to
the
need for
weather
protectíon, the ing
ress
iquids
partic
ulate
matter
co
rrosive
effect
of
solvents
a
nd
h
eat
7.3
adjacent
plants.
The
KOC-G-002
shall
be
referred
along
with
relevant
drawing
of
facility
for
hazardous
area
classification.
Only
certified
equipment
shall
be
setected
and
the
certification
shall
be
fãr
the
peak
amLienttemperature
also
marked
on
the
equipment
.4
DOC.
NO.
KOC-E-004
Pt.
5
Page
I
of
18
REV.
2
:.;:i,i
.
;til
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 10/19
c/*
{REV.
2
}
7.5
Electrical
Equipment
in
Hazardous
Area- Certification
Bodies:
For
details
of
Certification
Bodies
(Electrical
Equipment
in
Hazardous
Area) acceptable
to
KOC,
refer
Clause
9.15
of
*KOC
Recommended
Practice
for
Selection,
lnstallation
and
Maintenance
of
Electrical
Equipment
in
Hazardous
Areas
-Flameproof
Enclosure
d (KOC-E-004
ParI2,
Rev.
2).
7.6
The
maximum
temperature
appropriate to
the
temperature
class shall
not exceed
the
ignition temperature
of
the
flammable
gas
or
vapour
expected
to
be
present
in
the
hazardous
area.
lf more than one
flammable
gas
or
vapour
is
present
in the area
then
the lowest
value
of
the
ignition temperature
shall
be
considered.
7.7 The
temperature
of any external
or
internal
surface
to
which
the
explosive
atmosphere
has
access
shall
not exceed
200 C
(temperature
class
T3).
Where
gases
or
vapour having
an
ignition
temperature
below
200 C,
temperature
class
T4,
T5
or
T6
shall
apply.
The
rating
plate
shall
be clearly
marked
for
this
fact by
the
manufacturer.
7.8
Where
a
motor is
started
at
number of
times
each
day on
a
regular
basis,
account
shall
be
taken
of
the
temperature
reached
during the
starting period
to
assess the
temperature class.
7.9
Rotating
electrical
machines
fitted
with terminal
boxes
including
removable
covers,
shall
maíntain
the degree
of
protection
not less
than
lP
54
in accordance
with
BSEN
60529.
7.10
Apparatus
covered
under
protection n shall not
in
normal
operation,
produce
an
arc or
spark
unless
the
operational
arc
or spark
is
prevented
from causing
ignition
to
an
explosive
atmosphere
by
means
of
an
enclosed-break
device;
or the
operational
arc or
spark has
insufficient
energy
to
cause
ignition
to a
hydrogen/air
gas
m
under specified
test
conditions;
or
the
operational
arc
or
occurs
in
hermetically
sealed
enclosure.
7.11
Where
a
pparatus
is
protected
by
two
or
more types
of
includ
ing
rNt
or
tfì
then
¡t shall
be
selected
according
to
apparatus
group.
ln
s
uc
h
cases
the certifi
cat¡on
shal
indicate
the
which
the
apparatus
can
be
used
e
C,
,f
o
ú
þ
Þ
gases
or
vapours
n
REV.
2
age 9 of
18
Ã
DOC.
NO. KOC-E-OO4
Pr.
5
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 11/19
,o
z
,f
o
ú
(,
7.12
Sealed
or
encapsulated devices
shall
be
so
constructed
that they
cannot
be
opened
in normal
service
and shall
be
provided,
where
necessary,
with
external
connections
(i.e.,
flying
leads
or
external
terminals).
7.13
Luminaries
shall comprise
either
a
restricted
breathing
enclosure
or
an enclosure
with a
degree of
protection
lP
54
or a
combination
of
both.
7.14
Restricted
breathing
luminaries
shall incorporate
a
suitable
sealing
ring
for
use
with
cable
entries.
7.'15
Portable
luminaries
and
other
apparatus
containing
light sources
shall comply with the relevant
requirements of
BS
6941.
T.'1.6
Where
reflectors
and
protective
guards
are
used on
the
luminaries,
the
rneans
of attachment
shall
not
impair
the
restrictive
breathing
properties
of such luminaries.
T.1T
The
lampholders
shall
be
either
of the
non-sparking
or
enclosed-
break
type,
besides
compfying
with
the
safety and
interchangeability
requirement.
T.1g
Hermetically
sealed
devices
shal
satisff
the
criteria
for
compliance
to
BS
6941.
7.,19
Enclosed-break
lampholders
shall
ineorporate
an
enclosure
to
prevent
ignition
of
surrounding
flammable
atmosphere
when
the
lamp
is inserted
or removed.
l.ZO
Non-sparking
lampholders
shall
be
preferred
which
are
constructed
so that
the
risk
of
arc,
spark
or
hot spot
capable
of
creating
an
ignition
hazard
during
normaluse
is minimized.
7.z',,
lf bayonet
non-sparking
lampholders
are
used,
it
shall
be ensu
that
they
incorporate sprung contacts
and
the
springs are
not
only
means
of
carrying
current.
7.22
Bayonet
lam
pholder
shall
be
of type
that
the move
ment
of the
lamp
does
lead
to sparking
under
conditions
of
vibration or
temperature
change.
The
lampholders
with
Edison
Screws
(Es)
may also
be
considered.
7.2g
Starters
shall
be
of the
type
in
which
the
contacts
are
enclosed
in
a
herrnetically
sealed
glass
bottle
inside
a metal
or
plastic
canister.
Starter
holders
shallbe
of
the
non-sparking
.24
the
safety and
interchangeability
shall
conform
to
Page
10
of
18
OC.
NO. KOC-E-OO4
Pt.
5
REV.
2
Ø
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 12/19
o
,f
o
2
v
7.25 Both
starter
and holder
shall be mounted
within the
enclosure
in
such
a way
that the
assembly
is
adequately supported
to
prevent
movement under
the
conditions
of vibration.
The
contact shall
be
resilient
and
shall
provide
adequate
contact
pressure.
7.26
Luminaries
shall be
marked wíth
the lamp rating and
gas group
and
temperature
class.
They shall
be
provided
with warning
label
stating
DO
NOT
CHANGE
LAMP
WHEN
ENERGIZED .
8.0
INSTALLATIO-N
RESUIREMENTS
8.1
For
general
installation
recommendations,
refer
to
Part
I
of
this
document.
8.2
Metallic
conduit
systems
for
apparatus with
type
'n'
protection
should
be
installed in
accordance
with
the
recommendations
given
in
KOC-
E-004
Part
1.
8.3 Plastic
conduit
systems may
be
used
provided
it is
suitable for
particutar location
and it shall be
of
minimum
schedule 40.
Such
conduit
systems
shall
be
supported
throughout
their lengths'
Where
it
is
required
that
a
conduit
or
ducting
system is
used
in
conjunction
witlr
a restricted-breathing
enclosure.
The
conduit
seal
shall
be instatled
to
ensure
that requirements of
restricted
breathing
are
complied.
Metallic
ducting
and
trunking
shall be
adequately
bonded
throughout
its
length
and earthed.
Where
machines
are
provided
with
loose
leads,
sufficient
length
of
loose
leads
shall
be
provided
for future
re-connection
to
be
made.
lt
shall
be
ensured that
necessary
insulation,
specified
clearances
and
creepage
distances
are maintained.
For
rotating electrical
machines
operating
at
high
voltages'
boxes
including
removable
covers,
the cable
sealing
and
boxes
shallbe
made
of steel.
Fans,
fan
hoods,
ventilation
screens
etc.
shall
be
constructed,
and
fixed
so as
to
prevent
distortion
and
displacement
that
could
cause
impact,
sparking
orfriction
of
rotating
parts
against
stationary
parts.
For
all
types
of
cable
connection,
it shall
be
possible
to
remove
rotating
ãiectrical
machines
without
stressing
the
cable
or
breaking
any
cable
seal
provided.
8.4
8.5
8.6
8.7
8.8
8.9
DOC.
NO.
KOC-E-OO4
Fr. 5
REV. 2
age
11
of
18
çh
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 13/19
8.10
Connection
of cables to apparatus
shall
be
made
by means
of
cable
glands
suitable for the
cable size
and
the
environment
to
maintain
the
integrity
of
the
apparatus.
8.11
lf the
temperature
shall
exceed
70 C
at
the cable
or conduit entry
point
or
80oC
at
the branch
point
of conductors, then
a label shall
be
provided
on the outside
of the apparatus
as
a
guide
for
selection
of
cable
or conduit wiring
insulation
material.
8.12
Resilient
gasket
seals
shall be
positioned
so
that they
are not subject
to
mechanical
damage
under
normal operating
conditions
and
they
shall
retain
their
sealing
properties
over
the
expected
life
of
the
device.
8.13
Where required,
soft,
seal washers shall be used between the
gland
body
and
the apparatus
to
ensure
the
degree
of
protection
of
the
terminal
enclosure.
8.14
Connection
of conductors
to
the
apparatus
termínals
shall
be
made
in
accordance
with
the manufacturer s
recommendations.
8.15
Unless
permitted
by
the documents,
two
conductors
of different
cross
sections should
not
be
connected
into
one
terminal.
4.16
Conductors
shall be
terminated
using crimp
type
terminals.
Correct
sized crimped terminals shall
be
used.
Conductor cross section
and
required
current
ratings
shall
be
maintained-
g.1T
When
the
cable sealing
and dividing
box is filled
with
compound, the
clearances
and
creepage
distances
shall
comply
with
BS 5000 Part
16.
8.19
Unused
cable
entries
shall
be
closed with
suitable
plugs
that
maintain
the
degree
of
protection.
g.1g
Fuse
links
shall
be
considered
non-sparking
devices
if
they are non-
rewirable
or
non-indicating
cartridge
type
operating
within
their
8.24
rating.
Fuse-link
operated
at
greater than
60V
shall
be
mounted
in non-
sparking
enclosed
holders.
Fuse
link
operated
at
60V
or
less
shall be
mounted
in
non-sparking
enclosed
holders,
non-sparking
spring
holders
or
soldered
in
Place-
Correct
type
and
value
for
replacement
fuses
shall
be shown
adjacent
io
the
fuse
holders,
unless
the
fuses
are of
a non-
interchangeable
tYPe.
8.21
8.22
Enclosure
shall
be
capable
of
withstanding
assembly
operation
without
damage
to
seals
and
REV.2
age
12of
18
OC.
NO. KOC-E-004
ft.
5
,.1..
Vç
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 14/19
()
,Í
o
2
e
8.23
Enclosure containing fuses
shall
either
be
interlocked
so that
insertion or
removal
of
replacement elements
can be
carried out
only
with the supply
disconnected
or
the enclosure
shall carry
a
warning label
DO
NOT
REMOVE FUSE
WHEN ENERGIZED .
9.0
|NSPECTION.
IUAINTENANCE ANp
TESTING
To
minimize
the risk
of
ignition
by electrical
installation & equipment
in
Zone 2, an
efficient
inspection,
maintenance
and
testing
of equipment
and
systems
is
essential.
The
general
recommendations
for inspection,
maintenance
and testing
are
given
in Part
1 of
this
document
and
apply
equally
to
this
part.
lf
at
any time
there is a
change
in
area
classífication,
or
in
the
characteristics
of
the
flammable
material used
in
the
area,
or
if
the
apparatus
is moved from one
location
to
another,
a
check
should
be made
to
ensure
that
the
apparatus
has
the
correct
temperature
class,
group
and
continues
to comply with the
area
classification.
9.4
The
apparatus,
system
and
installation
shall
be
inspected
regularly in
accordance
with the relevant
items
in the detailed
'D'
(*
=
lnitial)
column
of
the
inspection
schedule,
given
in
Appendix
A.
9.1
9.2
9.3
9.5
9.6
9.7
9.8
Periodic
inspection
shall
be
carried out at
least
once
every
two
years.
More frequent
inspections
may
be
justified
when
the equipment
is
operating
under
corrosive
atmosphere
or
subject
to
excessive
temperature,
vibration
etc,.
The results
of
all
inspection
shall be
recorded
so
that
review
of
inspection
frequencíes
is effective.
No alteration
shall be
made
to apparatus
with 'n'type
protection
without
appropriate
approval.
Failure
to this might
invalidate
the
certificate
or
other document
relating
to the
safety
of
apparatus.
lf an
enclosed-break
device
is
known
to be
faulty
or
is
suspected
being
faulty,
the
device
shall be
discarded
areas.
lt
shall
be rePlaced
bY
a
new
design
and
characteristics.
from
further
service
ín
hazardous
certified
component
of equiva
Enclosed-break
devices
and
non-incendive
parts shall be subject
to
type test
in
accordance
with
BS
6941.
The
rating
of
e
devices
shall
be
limited
to
a maximum
rating
of
660V
and
154. The
incendive
parts
shall
be
limited
to
a
maximum
rating
of 250V
and
154.
g.g
Under
no
circumstances
an
enclosed-break
device
shall
be
repaired
or
renovated
for
further
service
in
hazardous
areas'
g.10
Rotating
machines
shall
be
maintained
in
accordance
with BS
5000
Part
16.
REV.2
age
13
of
18
OC. NO. KOC-E-004
Pt.
5
lr
çú
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 15/19
z
e
R
9.11
Where
there
is a requirement
for
working
on
apparatus
in the
energized
condition
(i.e.,
for
disconnecting,
maintenance, adjustment
or
testing)
provided
the
work
consists
of
minor routine
external
adjustments,
a
special
"work
permit" shall
be
obtained
certiffing that
the
area
is free
from flammable
gases
or vapours.
9.12
lf the work is
performed
on
or near de-energized
circuit
or equipment
where a
power
supply
could
be restored
inadvertently,
the lock
out-
tag out
procedure
shall
be
followed.
9.13
Where
practicable,
replacement
parts
and
fittings
should
be certified
or
approved
in
accordance
with'n'type
protection.
1O.O QUALITY
ASSURANCE
The
manufacturer
shall operate
a
quality
system
to
ensure
that
the
requirements
of
this
Standard
are
achieved.
The
quality
system
shall
preferably
be
based
on
ISO
9000
series
of
standards
and the
manufacturer
shall
demonstrate
compliance
by
providing
a
copy
of
the accredited
certificate
or
the
manufacturer's
quality
manual.
Verification
of the
manufacturer's
quality
system
is normally
part
of the
pre-qualification
procedure, and
is
therefore
not
detailed
in
the
core
text
of this
Standard.
11.0
MARKING
,11.1
Typical marking requirements
are
detailed in
KOC-E-004
Part
1.
The
apparatus
with
the type
of
protection'n'shall
be
permanently
marked
to
indicate
thefollowing
particulars
as
minimum.
.
ldentification
of
the manufacturer.
'
The
type
designation
of
the
apparatus.
.
The
number
of
the
relevant
certification
standard.
a
ldentification
of
the
type
of
protection
by
symbol:
Ex'nA
for
non-sparking
apparatus
Ex'nC'
for
sparking
apparatus
in
which
the contacts
are
protected
other
than
by restri
cted
breathing
enc
Ex'nR'
-
for
restricted
breathing
enclosure-
The
group symbol:
l
A,
ll
B or
ll G.
lf
the
apparatus
is
for
a
parüõuhi
gás
or
vapour
then
the
symbol
ll
shall
be
followed
by
the
name
or
chemicalformula
of
the
gas
or
vapour.
a
The
number
of the
certificate
and
the
issuing
a
Maximum
surface
temperature
in
degrees
Page
14 of
18
OC.
NO.
KOC-E-OO4
ft. 5
REV.
2
w
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 16/19
a
a
The
symbol
x,
if there
are
any
special
conditions
of installation
and
use
relevant
to the
safety.
This
shall
be
specified
in the
documents
of the
apparatus.
For luminaries,
the word
restricted
breathing
where applicable.
11.2
On
very
small electrical
apparatus
where
there
is limited
space,
the
marking
may be
reduced
but
it
shall require
at least,
The
symbol
Ex'n'together
with
A,
C
or
R.
The
name
or symbol
of
the certifuing
authority
and
the number
of
certificate.
.
The
symbolx,
if
apPlicable.
'
The
group
sYmbol.
.
The
temperature
class
or
maximum
surface
temperature.
.
The
name
or registered
trade
mark of
the
manufacturer.
11.3
For
other
detailed
information
on Packing,
Marking
and
Documentation,
refer
to
KOC-G-004.
12.0
DocuilENTATlON
12.1
All correspondence,
drawings,
instructions,
data
sheets,
design
calculations,
or
any
other
written
information
shall
be in
the
English
language.
1Z.Z
All
dimensions,
units
of
measurement,
physical
constants,
etc.
shall
be
in
Sl units,
unless
otherwise
specified-
,,2.g
The
following
documents
shall
be
obtained
from
the manufacturer:
r
I
certificate
fortype'n'issued
by an
appropriate
organization.
.
flllanufacturer's
claim
of
compliance
with
the
relevantstandard-
Apparatus
descriPtion.
Marking
and
any
other
information
normally
required
for
electrical
apparatus.
Additional
conditions,
if
any,
for
the
safe
installation
and
use
of
apparatus.
a
a
a
a
DOC.
NO.
KOC-E-Oo4
Pt. 5
Page
15 of
18
REV.2
w
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 17/19
z
,f
û
ÉR
12.4
Type
test certificates
for
the following
parts
of
the
apparatus
shall
be
obtained:
.
Enclosed-breakdevices.
.
Non-incendivecomponents.
.
Sealed,
hermetically
sealed
and
encapsulated
devices.
.
Energy
limited
apparatus
and
circuits.
.
Restricted-breathing
enclosures.
.
Screw lamp
holders.
13.0 SPARE
PARTS
MAINTENANCE
qArA
Refer
to
KOC
Standard
for
Spare
Parts
Maintenance
Data, KOC'G-009.
Page
16
of
18
OC. NCI.
KOC-E-OO4
Pt. 5
REV.
2
w
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 18/19
5.
lnlegrity
of
condult
rYstem
and Inter{aoewlth
mlxad
sYetem
ls
o
4.
boxes and
oable
boxee ara
correctlyf,lled.
toppor
3.
a
Seallng of
trunklng,
ducts'
PlPea
andlor
condults
is
satisfúotory.
a
2.
a
There
is no
obviou¡
damege
to
cablee.
1
B.
I
tNsTALLêTION
Tyæ
of
cebls
ls approprlats.
15.
a
Motor
fans have
sufrclent
clearanoe to
encloaure
andlor
covers.
14.
Re¡trlcted
breathing
enclosure
ls satiefiactory.
O
13.
a
Enolo¡ed
-
break
and
hermetlcally
sealed
devlces
ara
undamaged.
12.
a
Condltione
of enclosure
ga¡ksts
ls oatlsfactory
11.
Electrical connðctlons
are
tlght
t0.
Lamp
ratlng,
type
and
poaltlon
are
correct
-visual check
9.
Bolts,
cable entry
devices
(dlreot
and lndlrect)
and
blanking
elements are
of
the
correcttype
and are
complete and
tight
-
pfrysical
check
8.
a
There
are
no
vlslble
unauthorlzed modllications.
7.
I
There
are
no
unauthorized modiflcatlons.
6.
a
Enclosure,
glasses
and
glass
to metal
sealing
gaskets
andlor compounds
are
satisfactory.
5.
a
Apparatus
clrcult
ldentlficât¡on
ls
avallable.
4 Apparatus
clrcult
identiffcation
is correcL
3.
a
Apparatus
temperature
class is
correct.
2.
D
Apparatus
group
is correcl
1
A.
a
APPARATUS
Apparatus
ls approprlats
to area class¡flcat¡on.
*
v
ff
c
*
D
Grade
of
lnspection
heck
that:
APPENDIX A
INSPECTION
SCHEDULE
FOR
Ex'N'or
EEx'n'
Legend:
D
=
Detailed,
Q
=
Glose, V
=
Vlsual,'=Applicable
*=lnltial
=Periodic
REV.
2
age
17 of
'18
OC. NO.
KOC-E-OO4
Pt.
5
fr\
7/25/2019 KOC-E-004 Part-5
http://slidepdf.com/reader/full/koc-e-004-part-5 19/19
7-
TL
o
o
e
RN4
APPENDIX A contd..
INSPECTION
SCHEDULE
FOR
Ex N or
EEx n
Legend:
D
=
Detailed,
C
=
Close,
V=
Visual,.
=Applicable
*=lnitial
*=Periodic
Electrlcallngulatlon
ls clean and
dry.
.
a
No
undueaccumulation
of dustand dlrt.
.
a
ENVIRONTIENT
Apparatus
ls adequately
protected
againstcorroslon,
weather,
vibratlon
and
other adverse
factore.
c.
1
Special condltions
of lnstallat¡on and uss are complied
with
(if
applicable).1.
Automatlo
etectrical
protective
devlces
are
set correctl¡1.
0.
Automatic
electrical
protective
devlceg
operate within
permlttsd
lim¡ts.
.
lnsulation
reslstance
is salirfactory.
.
Fault
loop impedance
(TN
¡ystsms)
or earthlng
reslstance
(lT
systems) is
satisfactory.
7
INSTALI-ATION
oo¡td..
Earthlng
connectlons,
lncludlng
any
supplementary
earthing
bondlng
connections are satlsfactory
(e.9.,
connections
are
tight
and
conduotors
are
of
sumcient
cross aection).
-
physlcal
ohech
-vlsual
chsok
B.
6.
*t
v
*
c
*
D
Check
that:
Grade
of
lnspection
REV.
2
age
18
of
18
OC.
NO.
KOC-E-OO4 ft. 5