Abb - Sys600c

download Abb - Sys600c

of 42

Transcript of Abb - Sys600c

  • 7/23/2019 Abb - Sys600c

    1/42

    M ic ro SC AD A Pr o S YS 6 00 C 1 .9 3

    P ro du ct G ui de

  • 7/23/2019 Abb - Sys600c

    2/42

  • 7/23/2019 Abb - Sys600c

    3/42

    Contents:

    1 . C o p y r ig h t s . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . 5

    2 . I n t r o d uc t i o n . . . . . . .. . . . . . .. . . . . . .. . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. 6

    2 . 1 . T h i s m a n ua l . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . 6

    2 . 2. U s e o f s y mb o ls . . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . . 6

    2 . 3. A b b re v i at i o n s . . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . 6

    2 . 4. R el a te d d o cu me n ts . . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. 7

    2 . 5. D oc u me nt r e vi s io ns . . . .. . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . . 7

    3 . F u nc t io n al o v er v ie w . . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. 8

    3 . 1. P r oc e ss c o mm u ni c at i on . . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. 8

    3 . 2. S Y S 6 00 C w o r kp l ac e s . . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . 9

    3 . 2. 1 . W o r k pl a c e s . . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . 93 . 2. 2 . P r oc e ss D i sp l ay . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . 9

    3 . 2. 3 . E v en t D i sp l ay . . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . . 1 1

    3 . 2. 4 . A l ar m D i s p la y .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . 1 2

    3 . 2. 5 . B l oc k in g D i sp la y . . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . 1 3

    3 . 2. 6 . T re nd s D i sp l ay .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . . 1 4

    3 . 2. 7 . M e as u re m en t R e po r ts D i sp l ay . . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . 1 5

    3 . 3. U s er m a na g em e nt . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. 1 6

    3 . 4. L o ca l iz a t io n . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. 1 6

    3 . 5. Ti m e s y nc h ro n iz a ti o n . . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . . 1 6

    3 . 6. R e du n da n cy . . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . 1 7

    3 . 7 . M i r r o ri n g . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . .. . 1 73 . 8. O P C c o nn e ct i vi t y . . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . 1 8

    3 . 9 . C y b er s e c ur i t y . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . 1 8

    3 . 1 0. K e y b e n e f i t s . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . .. . . . . . .. . . 1 9

    4 . A p pl i ca t io n a re a s . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . . 2 0

    4 . 1. O v e rv i e w . . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . . 2 0

    4 .2 . S YS 6 00 C a s C om mu ni ca ti on G at ew ay . . .. .. .. . .. .. . .. .. .. . .. .. .. . .. .. .. . .. . 2 1

    4 . 3. S Y S 6 0 0C a s C o nt r ol S y st e m H S I . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. 2 2

    4 . 4. S Y S 6 0 0C a s C om m un i ca t io n S e rv e r . . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . 2 4

    5 . P r o d uc t s t r uc t u re . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . . .. . . . . . .. . . 2 6

    5 .1 . O rd er in g, d el iv er y, a nd l if e c yc le p ol ic y . .. . .. .. . .. .. .. . .. .. .. . .. .. . .. .. .. . .. .. . 2 6

    5 . 2. S o ft w ar e o pt i on s . . . . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . . 2 7

    5 .2 .1 . C om mu ni ca ti on p ro to co ls . .. .. . .. .. .. . .. .. . .. .. .. . .. .. .. . .. .. .. . .. .. . . 2 7

    5 . 2. 2 . H S I f e at u re s . . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . 2 8

    5 . 2. 3 . S y st e m f u nc t io n s .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . 2 9

    5 . 3 . C o m pu t e r o p t io n s . . . . . . .. . . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . . . . . .. . 3 2

    6 . H ar d wa re c h ar a ct e ri s ti c s . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . 3 4

    6 . 1. H a r d w ar e . . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . . 3 4

    3

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i deI s s u e d: 3 0 . 6 .2 0 1 0

    V e rs i o n : A / 3 0 .6 . 2 0 10

  • 7/23/2019 Abb - Sys600c

    4/42

    6 .2 . E MI / EM S a nd e nv ir on me nt al s ta nd ar d c om pl ia nc e . . .. .. . .. .. .. . .. .. .. . 3 5

    7 . C ap a ci t y a n d p er f or m an c e . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . 3 7

    7 . 1. S Y S 6 0 0C c a pa c it y . . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . 3 7

    7 . 2. D a ta l o gg i ng c a pa c it y .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . 3 7

    7 . 3. P r oc e ss c o mm u ni c at i on c a pa c it y . . . .. . .. . . .. . .. . . .. . .. . . .. . .. . . .. . . .. . .. . . .. . .. . 3 8

    4

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    5/42

    Copyrights1.

    The information in this document is subject to change without notice and should not be

    construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for anyerrors that may appear in this document.

    In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential

    damages of any nature or kind arising from the use of this document, nor shall ABB Oy

    be liable for incidental or consequential damages arising from use of any software or

    hardware described in this document.

    This document and parts thereof must not be reproduced or copied without written per-

    mission from ABB Oy, and the contents thereof must not be imparted to a third party

    nor used for any unauthorized purpose.

    The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.

    Copyright 2010 ABB. All rights reserved.

    Trademarks

    ABB is a registered trademark of ABB Group. All other brand or product names men-

    tioned in this document may be trademarks or registered trademarks of their respective

    holders.

    Guarantee

    Please inquire about the terms of guarantee from your nearest ABB representative.

    5

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    6/42

    Introduction2.

    T hi s m an ua l2.1.

    This manual provides product information on the Compact System SYS 600C (later

    referred to as SYS 600C). It gives an overview of the product functionality, key benefits,

    application areas, technical details, and capacity and performance.

    U s e o f s y mb o ls2.2.

    This publication includes the following icons that point out safety-related conditions or

    other important information:

    The information icon alerts the reader to relevant facts and

    conditions.

    Abbreviations2.3.

    Descr iptionAbbr eviation

    C o m pa c t f l a s hCF

    C e n t ra l P r o c e s si n g U n i tCPU

    D i st r ib u te d C o mm o n O b je c t M o de lDCOM

    D i s t ri b u t ed C o n t ro l S y st e mDCS

    D y n a mi c H o s t C o n f i gu r a t io n P r o t oc o lDHCP

    D u a l i n -l i n e p a c ka g eDIP

    Electromagnetic InterferenceEMI

    Electromagnetic ShieldingEMS

    H u m an S y s te m I n t e r f a ceHSI

    I n t e g ra t e d D r i ve E l e c tr o n i csIDE

    I n t e l li g e n t E l e c tr o n i c D e v ic eIED

    I n t e r ne t P r o t oc o lIP

    L i gh t E mi t ti n g D i od eLED

    M e an T im e B e tw e en F a il u reMTBF

    Network Control Center NCC

    O L E f o r P r oc e ss C o nt r olOPC

    P r o d uc t A u t h or i z a ti o n F i l ePAF

    6

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    7/42

    Descr iptionAbbr eviation

    Personal Computer PC

    Adobe Acrobat file formatPDF

    S i m pl e N e t wo r k M a na g e m en t P r o t oc o lSNMP

    S i m pl e N e t wo r k T i me P r o t oc o lSNTP

    P r od u ct n a meS YS 6 00

    P r od u ct n a meS YS 6 00 C

    Universal Serial BusUSB

    Related documents2.4.

    Document IDN a me o f t h e d o cu m en t

    1MRS756664S Y S 6 0 0 9 . 3 I E C 6 1 85 0 S ys t em D e si g n

    1MRS756634S Y S 6 0 0 9 . 3 I n st a ll a ti o n a n d A d mi n is t ra t io n

    Manual

    1MRS756646S Y S 6 0 0 9 . 3 S ys t em C o n fi g ur a ti o n

    1MRS757257S Y S 6 0 0 C U s er ' s G u id e

    Document revisions2.5.

    Histor yDateS o f t w ar e r e v i si o n

    number

    Version

    D o c um e n t c r e a te d30.6.20101.93A

    7

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    8/42

    F u nc t io n a l o v e rv i e w3.

    SYS 600C is a modular and scalable automation system that can be configured and

    tailored for various applications and needs. This chapter gives an overview of the mainfunctionality.

    P ro c es s c o m mu n i c ati o n3.1.

    The process communication is used to connect various process devices, such as IEDs,

    RTUs, PLC, and Meters to SYS 600C. A large selection of communication protocols

    and interfaces, such as IEC 61850, IEC 60870-5-10x, DNP 3.0, Modbus, LON, and SPA

    are supported. See 5.2.1,Communication protocolsfor the full list of supported protocols.

    The process communication is used to retrieve data from the connected devices, such as

    status indications, events, and analog values, as well as to write data to the devices, such

    as commands, set points, and parameters. The data retrieved through the process commu-

    nication can be archived, presented on the HSI, or forwarded to other systems.

    See 3.8,OPC connectivityfor more connectivity options.

    R e mote c o mmun i c a tio n

    The remote communication is used to connect SYS 600C to upper level systems, such

    as Network Control Systems. The most common protocols, such as IEC 60870-5-101/104,

    DNP 3.0, and RP570 are supported.

    See 5.2.1,Communication protocolsfor the full list of supported protocols.

    Communication gateway

    The communication gateway functionality provides a gateway between process devices

    and up to eight upper level systems (NCC). The main tasks of the gateway are signal

    rerouting and protocol conversions. SYS 600C also supports signal grouping and possib-

    ility to introduce custom mapping logic in the gateway engine.

    The following table lists the protocols that are supported by the gateway engine.Ta b le 3 . 1- 1 P r ot oc o ls s u pp or t ed by t h e g at e wa y e ng i ne

    TypePr otocol

    MasterSPA

    MasterL AG 1 .4 ( LO N)

    M a st e r a nd s l a v eIEC 60870-5-101

    MasterIEC 60870-5-103

    8

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    9/42

    TypePr otocol

    M a s te r a nd s l a veIEC 60870-5-104

    ClientIEC 61850-8MasterANSI X3.28 - AB (ABB)

    M a s te r a nd s l a veR P 5 70

    M a s te r a nd s l a veD NP 3 .0 ( Su bs et 3 )

    M a s te r a nd s l a veModbus

    ClientO P C D A , A & E

    ServerO P C D A , A & E

    S Y S 6 0 0C w o r k pl a ce s3.2.

    Workplaces3.2.1.

    SYS 600C can be equipped with 1 to 5 workplaces to be used at the same time. The

    workplace provides means for the operator to configure the system and supervise and

    interact with the process. Each SYS 600C computer can have a local workplace, but the

    workplaces can also be distributed to other computers and locations.

    The workstations can be distributed over a network using TCP/IP. It can be a LAN,

    internet, or mobile wireless communication.

    Each workplace can be used for engineering, supervision, and operation of the process.

    The possibilities are defined by the access rights given to the user in question. Also the

    layout and functions of the workplaces can be fully customized for each user.

    The distributed workplace concept is based on available remote access techniques, typ-

    ically Microsoft Terminal Server or Citrix Access Essentials. Any PC or other web-

    enabled device can be used as a workstation without installing any additional software.

    P r oc e ss D i sp l ay3.2.2.

    One of the display types of the workplace is the process display. The process display isused to represent the process and primary equipment, typically as a single-line diagram

    with graphical symbols for primary devices, such as breakers, disconnectors, and trans-

    formers. The process display is normally built with symbol libraries, but also customized

    symbols and displays can be built.

    The process display supports zooming, panning, and decluttering for efficient and clear

    visualization of the information.

    9

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    10/42

    Through the process display the user can continuously monitor the process, such as

    switches and measurements, as well as access the control dialogs to issue commands,

    set parameters, and so on.

    C_20090111. png

    Figure

    3.2.2-1

    Process Display

    S y s tem S e l f S up e r vi s i o n

    The System Self Supervision function shows the status of the various system components

    in a display for easy and fast system maintenance and fault localization. The display

    shows information about the base system, applications, redundancy, communication

    lines, IEDs, and so on. The system can also receive status information from any device

    or external software reporting to the Windows event log, for example, disks, power

    supplies, and computer boards. Communication equipment and peripheral devices that

    support SNMP can also be supervised by using an SNMP-OPC gateway.

    10

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    11/42

    A 060527. P NG

    Figure3.2.2-2An example of typical system supervision display

    Event Display3.2.3.

    The event display shows events stored in the event database, as shown in Figure3.2.3-

    1. It supports easy sorting and filtering of the events to make the event analysis as easy

    as possible. It can also be freely configured to display the information, the layout, and

    coloring of the events.

    It is also possible to have predefined filters that can easily be accessed from toolbars and

    menus.

    11

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    12/42

    C_20090112. png

    Figure3.2.3-1Event Display

    A l ar m D i sp l ay3.2.4.

    The alarm display shows the alarms of the system in a list, as shown in Figure3.2.4-1.

    It supports easy sorting and filtering of the events to make the alarm analysis as easy as

    possible. It can also be freely configured to display the information, the layout, and col-

    oring of the alarms.

    It is also possible to have predefined filters that can easily be accessed from toolbars and

    menus.

    12

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    13/42

    C_20090113. png

    Figure3.2.4-1Alarm Display

    Blocking Display3.2.5.

    The blocking display lists all active blockings in the system. The display can also be

    used to activate new blockings. The following aspects of a signal can be blocked:

    updating, control, event logging, alarm generation, event printout, and post-processing.

    13

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    14/42

    C_20090114. png

    Figure3.2.5-1Blocking Display

    Tr e n ds D i s p la y3.2.6.

    The trends display is an application that collects data and visualizes the data in a

    numerical or graphical form. It is used for following up and analyzing data in time frames

    from minutes to one month. The data is logged cyclically in intervals of 30 seconds, 1,

    2, 5, or 10 minutes. The trends display can log and show any type of data available in

    the process database.

    14

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    15/42

    A 050224. jpg

    Figure3.2.6-1Trends Display

    M e a su r e men t R e p o r ts D i s p la y3.2.7.

    The measurement reports display is an application that collects data and visualizes the

    data in a numerical or graphical form. The measurement reports display is used to logand report data during longer periods than the Trends Display, and it is dedicated for

    energy, current, voltage, temperature, and frequency reports.

    The available time ranges for the reports:

    Hourly report (time resolution: 1, 2, 3, 5, 6, 10, 15, 20 or 30 minutes)

    Daily report (time resolution: 15, 30 or 60 minutes)

    Weekly report (time resolution: 1 day)

    Monthly report (time resolution: 1 day)

    Yearly report (time resolution: 1 month)

    Quick Report on an hourly basis (time resolution: according to a period cycle)

    Quick report on a daily basis (time resolution: according to a period cycle) )

    Quick report on a weekly basis (time resolution: 1 day)

    Quick report on a monthly basis (time resolution: 1 day)

    Quick report on a yearly basis (time resolution: 1 month)

    15

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    16/42

    C_20090116. png

    Figure3.2.7-1Measurement Reports Display

    U s er m a na g em e nt3.3.

    Users of the system are given access rights according to the needs. The user sessions

    can be limited in time. The users can be given the right to view, control, or configurethe different parts of the system or process.

    Localization3.4.

    It is possible to translate the user interface to any language that fits into the boundaries

    of the graphical user interface, that is, size, position, and direction of texts and icons.

    The system also supports several languages simultaneously enabling operators to work

    with the system in their native language. The language is part of the user profile and is

    selected automatically while logging into the system.

    T i me s y n c hro n i za ti o n3.5.

    SYS 600C can be synchronized by an external GPS clock. This is typically done using

    SNTP over the local area network or through a serial port using a protocol provided by

    the clock manufacturer. It is also possible to add a PCI card into the computer to retrieve

    the clock signal. The IEC 61850 client of SYS 600C includes an SNTP client that can

    be used to set the system clock. SYS 600C can also be synchronized by the Network

    Control System over a remote communication protocol.

    16

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    17/42

    SYS 600C can also be used as a clock master for the connected IEDs according to the

    used protocol.

    Redundancy3.6.

    S y s tem r e d un d a nc y

    The availability of a SYS 600C system can be further improved by redundant servers

    configured in a hot stand-by mode (HSB). In this configuration, one computer is active

    and receives and processes all data from the process. It also manages the displays and

    provides data for the displays. At the same time, all process data and configuration data

    is shadowed over to the stand-by computer. The stand-by computer is in the same state

    as the active one. If the active computer breaks down, the stand-by computer takes over

    the process communication and continues to manage the process. In this way, the processcan be operated and supervised even if one of the computers fails.

    Communication redundancy

    Redundant communication lines mean that two or several connections between the

    master and the slave form a logical connection. One of the connections is active and if

    the active connection fails, another connection is used instead.

    Redundant communication lines are supported for IEC 60870-7-101 slave, RP-570 slave,

    and IEC 60870-7-104 master and slave protocols.

    Redundant LAN connections are supported for, for example, IEC 61850 communication

    using dual LAN connections according to IEC 62439/PRP. See SYS 600 IEC 61850

    System Design for details.

    The network chipset used in the SYS 600C supports Intel Teaming with Advanced

    Networking Services. Teaming can be used to provide additional fault tolerance in case

    of a port or a switch failure, as well as for load balancing and link aggregation. The

    restrictions and possibilities of interface teaming are described in the Intel Advanced

    Networking Services documentation.

    Mirroring3.7.

    The process data mirroring provides powerful means for sharing process data in a SYS

    600C/SYS 600 network with minimal engineering effort. This can be used to build

    hierarchical systems, for example, with one main control center, some regional control

    centers and more local control centers or substations. It can also be used for load distri-

    bution in large systems. The data mirroring can also be used to share data between a

    SYS 600C HSI and SYS 600C Gateway, for example, when communication protocols

    with one master are used.

    17

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    18/42

    The advantage of using data mirroring instead of standard communication, such as IEC

    60870-5-104, is that the data mirroring communication is much more efficient and the

    required engineering work to build up the system is minimal. Several special functions,

    such as event buffering during communication breaks and handling of hot stand-by

    configurations, are automatically taken care of.

    The data mirroring takes place between a host and an image. The host is the source for

    the process data and the image is a copy of the process data. The SYS 600C node that

    receives the process data, for example, through IEC 61850 or LON, is the host. This

    process data can be mirrored to another SYS 600C node, which acts as an image.

    OPC connectivity3.8.

    OPC is a de-facto interface standard connecting various devices and systems within the

    process automation industry. OPC is becoming more and more used and accepted alsoin other application areas and within the power industry. It defines exchange of data

    between a server and a client. The server provides data and the client uses the data. The

    client can also write data (commands, parameters, and so on) to the server.

    SYS 600C provides OPC connectivity both in forms of clients and servers, that is, SYS

    600C can receive data from a device or system that provides its data through an OPC

    server. SYS 600C can also provide its data to another system that acts as a client.

    C y be r s e cu r it y3.9.

    The product is designed to fulfill high cyber security requirements. It supports the fol-

    lowing functions:

    User authentication

    Configurable password policies

    Encrypted user name and password

    Configurable Use Banners

    User Authorization

    Users can be granted access rights to functions as required

    Communication encryption

    Encryption of TCP/IP connections (IPSec/VPN)

    Virus protection Operating System Security Patching

    System hardening

    Closing of unused ports and services

    Security policies

    Robustness testing as an integrated part of the development process

    18

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    19/42

    K ey b en ef it s3.10.

    SYS 600C offers the following highlights and key benefits:

    Solid-state hardware technology Enables use in harsh environments

    Reduces maintenance needs

    Support for wide operating temperature range

    Scalability

    Enables system sizes ranging from tens to thousands of data points

    Flexible system configuration, ranging from communication gateway to control

    system HSI solution with integrated communication gateway functionality to

    communication server in large SA system and network control system

    Conformance to a wide range of communication standards and de-facto com-

    munication standards

    Powerful hardware with large number of serial and ethernet interfaces

    High availability

    Proven and tested hardware with high MTBF value

    Support for redundant (Hot Stand-By) system servers

    Support for redundant remote communication lines

    Support for redundant power supplies for both AC and DC power supply

    Engineering efficiency

    Integrated tools for system engineering, for example expansion of databases,

    communication system, HSI clients, and users

    Support for third-party software and hardware through the use of open interface

    and communication

    Easy to upgrade with latest software versions that enable use of new and

    innovative functionality Powerful HSI

    Powerful data collection to be used in single line diagrams, process displays,

    trends, reports, control, alarms, and events

    Process displays with support for zoom/pan/de-clutter

    Trends with zoom/pan, multiple graph types, ruler, cut, and paste

    19

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    20/42

    Application areas4.

    Overview4.1.

    SYS 600C provides innovative solutions for different tasks and operations in the power

    automation process, from Communication Gateway functionality to full-fledged

    redundant control system applications. SYS 600C is a solid-state computer utilizing

    information distributed in different locations and hence enabled for a large variety of

    tasks. SYS 600C is suitable in, for example, Substation Automation Systems for both

    Utility and Traction applications, as well as in Process Industries with distributed Intel-

    ligent Electronic Devices (IEDs). SYS 600C is also designed to be used as a Communic-

    ation Server in medium and large Remote Control Systems (SCADA).

    SYS 600C is designed as an open system, which complies with all widely used commu-

    nication standards. In addition, it supports the implementation of project-specific monit-

    oring, control, and automation tasks in the field of Substation Automation and Power

    Automation. The SYS 600C Human Machine Interface (HSI) provides an intuitive and

    easy-to-use user interface for efficient and safe operator actions.

    The consistent use of known technologies and intuitive user interfaces ensures an easy

    entry level for new SYS 600C users.

    F i e l ds o f a p p l ic a ti o n

    SYS 600C is designed to be used in a wide range of applications in both Electrical Util-ities and Industries.

    When using SYS 600C in substations, the main application is as a Communication

    Gateway to the upper level system or it is used as a powerful Control System HSI. The

    two can also be combined in the same SYS 600C system and forms hence a combined

    Communication Gateway with Control System HSI. SYS 600C can be used in any type

    of substation.

    In large substations and in medium- and large-sized remote control systems, SYS 600C,

    thanks to the large amount of communication ports, is an unbeatable Communication

    Server solution (also known as a front-end computer).

    SYS 600C fits also well into various types of control applications, especially where a

    solid-state type of computer is required and different kinds of distributed Intelligent

    Electronic Devices (IEDs) together with other type of bay devices (RTU) are to be con-

    nected to the system. Connections to process automation systems are well supported in

    SYS 600C thanks to OPC server and client integration.

    20

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    21/42

    S Y S 6 0 0C a s C o mm u ni c at i on G a te w ay4.2.

    SYS 600C is used for multiple purposes at a substation level. The Communication

    Gateway function is one of the tasks that can be utilized at the substation level to enableconnections to Remote Control Centers (SCADA). SYS 600C Communication Gateway

    can connect to, and interact with, eight (8) different Remote Control Centers.

    The SYS 600C Communication Gateway function can be configured as a single gateway

    as shown in Figure4.2-1.

    C_20090101. bmp

    Figure

    4.2-1

    SYS 600C as Communication Gateway

    Utilizing the OPC interface in SYS 600C enables an easy and efficient integration of

    IED signals and information into a DCS system, as shown in Figure4.2-2.

    This configuration is typically applied in Process Industries with distributed Intelligent

    Electronic Devices (IEDs).

    C_20090102. bmp

    Figure4.2-2SYS 600C Communication Gateway interface to Distributed Control Systems (DCS)

    21

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    22/42

    For increased availability, SYS 600C can easily be configured as a redundant Commu-

    nication Gateway as shown in Figure4.2-3.

    C_20090103. bmp

    Figure

    4.2-3

    SYS 600C as Redundant Communication Gateway

    SYS 600C also supports redundant remote communication lines between SYS 600C and

    Remote Control Center as shown in Figure4.2-4.

    C_20090104. bmp

    Figure

    4.2-4

    SYS 600C as Communication Gateway with redundant communication lines to

    Remote Control Center

    SY S 6 00 C as C ont ro l S ys te m HS I4.3.

    SYS 600C HSI provides numerous options for monitoring and controlling a connected

    process. SYS 600C handles both the HSI functionality and the Communication Gateway

    functionality. In this way SYS 600C can act both as a Communication Gateway, enabling

    a remote connection to control centers, as well as the local control system and HSI user

    interface on a station level.

    The SYS 600C HSI function can be configured as a single and local Control System HSI

    configuration as shown Figure4.3-1.

    22

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    23/42

    C_20090105. bmp

    Figure

    4.3-1

    SYS 600C as Control System HSI

    To reduce the number of devices at the substation level, SYS 600C Control System HSI

    and the Communication Gateway function can be combined in the same computer as

    shown in Figure4.3-2.

    C_20090106. bmp

    Figure

    4.3-2

    SYS 600C as combined Control System HSI and Communication Gateway

    For increased availability, SYS 600C can be configured as a redundant Control System

    HSI and integrated Communication Gateway with redundant communication lines to

    Remote Control Center as shown in Figure4.3-3.

    C_20090107. bmp

    Figure4.3-3SYS 600C as redundant Control System HMI and integrated Communication Gateway

    SYS 600C can also be utilized as an HSI for station RTU as shown in Figure4.3-4.

    23

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    24/42

    C_20090108. bmp

    Figure4.3-4SYS 600C as Control System HSI for RTU

    S Y S 6 0 0C a s C o mm u ni c at i on S er v er 4.4.

    SYS 600C can function as a powerful Communication Server in medium and large

    Remote Control Center configurations as well as in large Substation Automation

    applications.

    SYS 600C with its large number of serial communication ports and LAN ports in com-

    bination with the solid-state technology offers an excellent Communication Server

    solution. The Communication Server solution is offered and available as a part of larger

    SYS 600 or SYS 600C configurations as shown in Figure4.4-1and Figure4.4-2.

    C_20090109. bmp

    Figure4.4-1SYS 600C as Communication Server in a Remote Control Center system

    24

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    25/42

    C_20090110. bmp

    Figure4.4-2SYS 600C as Communication Servers in a large Substation Automation system

    By utilizing the SYS 600C Communication Server solution the processing load in the

    main system servers SYS 600 or SYS 600C is reduced. The Communication Servers are

    connected to the process devices and provide the main system servers SYS 600 or SYS

    600C with process information.

    25

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    26/42

    Product structure5.

    O rd er in g, d el iv er y, a nd l if e c yc le p ol ic y5.1.

    SYS 600C is a product that combines the robust solid-state computer with the operating

    system and the SYS 600 software.

    Computer

    The computer exists in a number of fixed configurations that is selected during ordering.

    The fixed configurations concern the parts supplied by the ABB product unit. There are

    no options that can be ordered separately.

    To replace the faulty SYS 600C computers, customers with SYS 600C products can onlyorder a SYS 600C spare computer without the SYS 600 license. If the SYS 600C computer

    configuration needs to be changed for some reason, the only possibility is to order a

    spare computer and replace the original one with the spare one.

    SYS 600C has three PCI slots for additional PCI cards. SYS 600C does not include any

    additional cards by default. Additional cards, such as the XLON card, can be purchased

    from external suppliers.

    Operating systems

    The operating system can be upgraded after the delivery. The operating system upgrades

    are not delivered from the ABB product unit, but can be purchased from an external

    supplier. The operating system must be compatible with both the computer and the SYS

    600 software. Operating system security updates can be applied, but operating system

    service pack must be approved for the SYS 600 software.

    S YS 6 00 s of tw ar e

    The SYS 600 software can be extended or upgraded to new versions. This is done with

    the normal ordering tool with the upgrade/extension options. SYS 600 Hotfixes, and

    Service and Feature Packs can also be freely taken into use. New SYS 600 versions willbe available for the SYS 600C hardware for at least 4 years after the hardware delivery.

    After that new SYS 600 software versions may require an upgrade of the hardware.

    The SYS 600 software license is bound to the Hardware Key that is installed inside the

    computer.

    26

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    27/42

    Product identification

    The SYS 600C product is identified by the computer version and the SYS 600 software

    version.

    Example: SYS 600C 1.93 Hardware version 1, SYS 600 software version: 9.3

    S o ft w ar e o p ti o ns5.2.

    Communication protocols5.2.1.

    The following tables list the communication protocols of SYS 600C.

    Ta b le 5 . 2. 1 -1 M as t er p r ot oc o ls

    M a s t e r p r o t oc o l

    I E C 6 1 85 0 - 8 -1 C l i e n t

    LON/LAG

    S PA B u s

    IEC 60870-5-101

    IEC 60870-5-103

    I E C 60 8 7 0 -5 - 1 0 4, S i n g l e o r r e du n d a nt

    D NP 3 .0 L AN /WA N

    D NP 3 .0 S er ia l

    Modbus RTU

    Modbus TCP/IP

    R P 5 7 0/ 5 71

    ANSI X3.28 FD/HD

    P214

    ADLP 180

    I E C 6 1 10 7 ( m e t er i n g )

    Alpha Meter protocol

    RCOM

    Ta b le 5 . 2. 1 -2 S l av e p r ot o co l s

    S l a v e p r o t oc o l

    I E C 60 8 7 0 -5 - 1 0 1, S i n g l e o r r e du n d a nt

    I E C 60 8 7 0 -5 - 1 0 4, S i n g l e o r r e du n d a nt

    D NP 3 .0 L AN /WA N

    27

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    28/42

    S l a v e p r o to c o l

    D NP 3 .0 S er ia l

    R P 5 70 S in gl e o r r e d un da nt /R P 5 71F 4 F W es t i n gh o u s e, N o g a t e wa y s u p po r t

    Modbus RTU (CPI)

    H S I f e at u re s5.2.2.

    The following table lists the SYS 600C HSI features.

    Ta b le 5 . 2. 2 -1 U s er i n te r fa ce o p ti o ns

    ValueDescr iptionU s er i n te r fa c e o p ti o n

    0...5T h i s i s t h e n u m be r of w o r k-p l ac es t h at a r e i n u s e s i mu l ta n -

    e o us l y. T h e n u mb e r o f w o rk -

    p l a c es n e e d ed i s d e f i ne d i n t h e

    f o ll o wi n g w a y: - A w o rk p la c e

    m e a n s a c o m pu t e r ( P C,L a pt o p, P DA , T h in C li e nt ) ,

    w hi ch c an h av e o ne o r se ve ra l

    physical screens from where

    ON E p ers on a t a t ime ca n

    o p e r a te . - S e v e r a l A p p l i c at i o n

    W in do ws c a n b e u se d i n o neworkplace.

    N r of P r o w o rk p la c es

    Yes/NoS el ec t t hi s op ti on , i f y ou w an tt o u se P ro ce ss D is pl ay s i n t heworkplaces. Process Displays

    means displays with zooming,

    p a n n in g , a n d d e c lu t t e ri n g f u n c-

    t i o n s t y p i ca l l y u s e d t o p r e s en t

    t h e p r im ar y p r o ce s s, f o r e x a mp l e , s i n g le - l i n e d i a g ra m .

    Process displays

    Yes/NoS el ec t t hi s op ti on , i f y ou w an t

    t o u s e d y na m ic ne t wo r k c o lo r -i n g i n t h e P r oc e ss D i sp l ay s .

    Network coloring

    Yes/NoS el ec t t hi s op ti on , i f y ou w an t

    t o u se t he Tr en d d is pl ay s i n t heWorkplaces.

    Trends

    Yes/NoS el ec t t hi s op ti on , i f y ou w an t

    t o u se t he E ve nt L is t d is pl ay si n t h e W or k pl a ce s .

    E v en t l i st

    Yes/NoS el ec t t hi s op ti on , i f y ou w an t

    t o u se t he A la rm Li st d is pl ay si n t h e W or k pl a ce s .

    Alarm list

    28

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    29/42

    ValueDescr iptionU s er i n te r fa c e o p ti o n

    Yes/NoS el ec t t hi s o pt io n, i f y ou w an tt o u se t he B lo ck in g L is t d is -

    p l ay s i n t h e W or k pl a ce s .

    B l o c ki n g l i s t

    Yes/NoS el ec t t hi s o pt io n, i f y ou w an tt o u s e t h e M e as u re m en t R e po r t

    d i s p la y s i n t h e W o r kp l a c es .

    T h is o p ti o n r e qu i re s t h e H i st o ry

    D a ta L o gg i ng o p ti o n.

    M e a su r e me n t r e p o rt s

    Yes/NoS el ec t t hi s o pt io n, i f y ou w an t

    t o i n te g ra t e P CM 6 00 To o ls i n

    t h e P r o c es s D i s p l a ys .

    P C M 6 0 0 i n t e r fa c e

    Yes/NoS el ec t t hi s o pt io n, i f y ou w an t

    t o i n te gr at e L IB 5 10 /5 42 I ED

    To o l s i n t h e W o r kp l a c e.

    I f y ou u se o nl y th e I ED t oo ls i n

    t h e W or k pl a ce , n o o t he r L I B

    l i ce n se i n n e ed e d.

    L I B 5 1 0/ 5 42 I E D To o ls

    Yes/NoS el ec t t hi s o pt io n, i f y ou w an t

    t o i n te gr at e L IB 5 20 I ED To ol s

    i n t h e W or k pl a ce .

    I f y ou u se o nl y th e I ED t oo ls i n

    t h e W or k pl a ce , n o o t he r L I Bl i ce n se i n n e ed e d.

    L I B 5 2 0 I E D To o ls

    Yes/NoS el ec t t hi s o pt io n, i f y ou w an t

    t o i n te gr at e L IB 5 30 I ED To ol si n t h e W or k pl a ce .

    I f y ou u se o nl y th e I ED t oo ls i n

    t h e W or k pl a ce , n o o t he r L I B

    l i ce n se i n n e ed e d.

    L I B 5 3 0 I E D To o ls

    S y st e m f u nc t io n s5.2.3.

    The following tables list the SYS 600C system functions.

    Ta b le 5 . 2. 3 -1 S y st em s i ze p a ra m et er s

    ValueDescr iptionS y s te m s i ze p a ra m et e rs

    1 .. 20 0 00

    G a t e wa y f u n c ti o n a l it y ( C O M

    5 0 0 i ) s u p p or t s m a x im u m 1 4

    0 00 i nd ic at io ns a n d 1 4 0 00c o m ma n d s c o n fi g u r e d w i t h in

    S Y S 6 0 0C .

    N u m be r o f p r o ce s s o b j e ct s

    c on ne ct ed t o t he p ro ce ss

    Process I/O

    29

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    30/42

    Ta b le 5 . 2. 3 -2 S ys t em o pt i on s a nd i n te r fa ce s

    ValueDescr iptionS y s t e m o p t i on a n d i n t e r f a ce

    Yes/NoT h i s o p t i on e n a b le s c o n t r olc o mm a nd s t o b e i s su e d f r om

    t h e s ys t em .

    T h is o p t io n s h ou l d n o rm al l y b e

    s el ec te d. T hi s o pt i on c an b e l ef t

    o u t i n p u r e m o ni t o ri n g s y st e ms ,

    w he re n o o ut pu t p ro ce sso b j e ct s a r e n e e d ed .

    Yo u a ls o n ee d t hi s o pt io n i n

    g a t ew a y s ys t em s , i f c o mm a nd s

    a r e p r op a ga t ed t h ro u gh t h e

    gateway.

    Control

    Yes/NoT h is o p ti o n a l lo w s 1 0 0 0 0 0 0 0e n tr i es o f h i st o ry d a ta t o b e

    a r ch i ve d ( D at a o b je c ts ) . T h is

    o p t i o n i s n e e d e d f o r e x a mp l e ,

    f o r t h e M e a su r e me n t R e p o rt s .T hi s o pt io n i s n ot n ee de d f or

    t h e s t an d ar d T re n ds .

    W i th o ut t h is o p ti o n, t h e n u mb e r

    o f D at a O bj e ct e n tr i es i s l i mi t ed

    t o 1 00 0 00.

    H i s to r y D a t a L o g g i ng

    Yes/NoS el ec t t hi s op ti on , i f y ou h av e

    a r e du n da n t p a ir o f s e rv e rs

    u s i n g t h e H o t - St a n d - By f u n c -tion.

    Hot-Stand-By redundancy

    (HSB)

    Yes/NoT h is o p ti o n s ho u ld b e s el e ct e d,

    i f t he d at ab as e m ir ro ri ng f un c-

    t i on s ar e u s ed a n d t h is s ys t em

    a ct s a s a H os t. T he H os t i s t hes y s te m t h a t p r o vi d e s p r o c es s

    d a ta t o a n ot h er s y st e m.

    F o r e x am p le , i f y o u u s e m i rr o r-

    i n g b e tw e en a c o mm u ni c at i on

    s e rv e r ( f r on t - en d ) a n d a s y st e m

    s e r ve r, t h e c o m mu n i c at i o n

    s e r ve r i s t h e h o s t .

    D a ta b as e m i rr o ri n g H O ST

    30

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    31/42

    ValueDescr iptionS y s t e m o p t i on a n d i n t e r f a c e

    Yes/NoT h is o p ti o n s h ou l d b e s e le ct e d,i f t he d at ab as e m ir ro ri ng f un c-

    t io ns a r e u se d a nd t hi s s ys te ma c ts a s a n I m ag e . T h e I ma g e

    i s t h e s y s te m t h a t r e c ei v e s

    p r o ce s s d a t a f r o m a n o th e r

    system.

    F o r e x am p le , i f y o u u s e m i rr o r-i n g b e tw e en a c o mm u ni c at i on

    s er ve r a nd a s ys te m s er ve r, t h e

    s y st e m s e r ve r is t h e I m a ge .

    D a t a ba s e m i r ro r i n g I M A GE

    Yes/NoT h is o p ti o n e n ab l es t h e O P C

    D A s e rv e r fu n ct i on . T h e o p ti o n

    s ho ul d b e s el ec te d, i f t he s ys -

    t em i s t o b e c on ne ct ed t o a ne x t e rn a l O P C D A C l i e n t ( f o r e xa mp le , 8 00 xA , H IS 6 00 )

    O P C D A S e r v er

    0...3T h is o p t io n i s p r im a ri l y i n t en d ed

    f or HS B s ys te ms , t o w hi ch a ne x t e rn a l OP C DA c l i e nt i s co n -

    n e ct e d ( f or e x am p le , H I S 6 0 0) .

    This Application OPC server is

    i ns ta ll ed i n t he O PC DA C li en t

    c o mp u t er a n d p r ov i de s a n O P C

    D A s e rv e r i n te r fa c e t h at a u to -

    m at i ca l ly co n ne c ts t o t h e H o ta p pl i ca t io n o f t h e H S B s ys t em .

    N ot e: T he re i s N O A &E s er ve r

    i nt er fa ce i n t hi s o pt io n.

    Application OPC Server

    Yes/NoT h is o p ti o n e n ab l es t h e O P CA&E server function (Alarms &

    E ve nt s) . T he o pt io n s ho ul d b e

    s el ec te d, i f t he s ys te m is t o b e

    c o nn e ct e d t o a n e x te r na l O PC

    A&E Client (e.g. 800xA)

    O P C A & E S e r ve r

    31

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    32/42

    ValueDescr iptionS y s t e m o p t i on a n d i n t e r f a ce

    0...4T hi s is a D A C li en t t ha t i sl o os el y c o up l ed t o t h e S YS 6 0 0

    b a s e s y st e m a n d c a n t h e r ef o r eb e i ns ta ll ed a ls o i n a s ep ar at e

    computer.

    I t i s u se d t o c on ne ct O PC D A

    s er ve rs t o S YS 6 00 . Yo u n ee d

    o n e c l ie n t f o r e a ch s e rv e r t h ati s t o b e c o nn e ct e d.

    N o te : T h is D A c l ie n t i s u s ed

    w it h t he I EC 61 85 0 O PC

    se rve r, b ut y ou d o n ot ha ve t o

    s el ec t t hi s o pt io n d ue t o t he

    I E C 6 1 8 5 0 c o m mu n i c at i o n .

    O PC D A C l ie n t / E xt e rn a l

    0...4T he O PC D A c li en t i s u se d t o

    c on n ec t f o re i gn d e vi c es t o S YS

    6 0 0 w it h t h e O PC D A i n te r fa ce .

    Yo u n ee d o ne c li en t f or ea chs e rv e r t h at i s to b e c o nn e ct e d.

    T h e D A c l ie n t i s t i gh t ly in t eg -

    r at ed w it h t he p ro ce ss d at a-

    b as e a nd r un a lw ay s o n t he

    S Y S 6 0 0 c o mp u te r.

    O PC D A C l ie n t

    0...4T he O PC A &E c li en t i s u se d t o

    c on n ec t f o re i gn d e vi c es t o S YS

    6 0 0 b y me a ns o f t h e O P C A & Einterface.

    Yo u n ee d o ne c li en t f or ea ch

    s e rv e r t h at i s to b e c o nn e ct e d.

    O P C A & E C l i e nt

    Yes/NoT he S QL E xp or t o pt io n

    p r o v id e s a t o o l a n d f u n c ti o n s

    f o r b r o ws i n g t h e p r o ce s s d a t a -b a se a n d e x po r ti n g p r oc e ss

    d a ta t o a r e la t io n al d a ta b as e .

    T he e xp or t c an b e d on e e it he r

    e v e n t b a s e d o r c y cl i c a l ly.

    S QL E x po r t

    C o mp u te r o p ti o ns5.3.

    The SYS 600C computer options are presented in the following tables.

    Ta b le 5 . 3- 1 H a rd wa r e

    Har dwar e

    P o we r S u pp l y: 8 8 - 13 2 VA C / 4 5 - 16 0 V DC (S i ng l e o r r e du n da n t)

    32

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    33/42

    Har dwar e

    P o we r S u pp l y: 1 7 6 - 26 4 VA C / 2 0 0 - 37 0 V D C ( S in g le o r r e du n da n t)

    E t he r ne t p o rt s 6 x R J4 5E th er ne t p or ts 2 x RJ 45 + 4 x LC

    T ab l e 5 . 3 -2 O p er a t in g s y st e m s

    Oper ating system

    W i n d o ws X P P r o f es s i o na l , E n g l i sh v e r si o n

    W i n d o ws X P P r o f es s i o na l , C h i n es e v e r si o n

    W i n d o ws S e r ve r 2 0 0 3, E n g l is h v e r si o n

    W i n d o ws S e r ve r 2 0 0 3, C h i n es e v e r si o n

    33

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    34/42

    H a rd w a re c h a ra c t er i st i c s6.

    Hardware6.1.

    The following tables lists the SYS 600C hardware characteristics.

    T ab l e 6 . 1 -1 H a r dw a r e s p e ci f i ca t i on s a n d d i m en s i on s

    I nt el C or e 2 D uo 2 .2 GH z ( T7 40 0)CPU

    I n te l 8 2 94 5 GM a n d I C H7 RChipset

    2 GB D DR 2Memory

    I n te l 8 2 94 5 c h ip s et i n te g ra t ed g r ap h ic c o nt r ol l er VGA

    Award BIOSBIOS

    1 x 1 6 GB W D S il i co n Dr i ve I I C F S SD - C1 6 GI - 43 0 0S t o r ag e d e v i ce

    3 x PC I v 2. 3 s lo tsE x p an s i o n s l o t

    1 6 x RS 23 2 a t r ea r pa ne lSerial ports

    6 x Gi g ab i t E t he r ne t ( R J4 5 o r L C ) a t r e ar pa n el

    1 x G i ga bi t E th er ne t a t f ro nt p an el ( R J4 5)

    1000M/100M/10Mb/s (RJ45)

    1000Mb/s (LC)

    LAN ports

    2 x US B a t r ea r p an el ( US B 2 .0 )

    1 x U SB a t f ro nt p an el ( US B 2 .0 )

    1 x U SB i nt er na l ( US B 2 .0 )

    USB

    AC97 2.1Audio

    PS/2Keyboard/Mouse

    S YS 6 0 0C u s es t h e o p ti c al i n du s tr i al g r ad e S FP c on n ec to r m od u le F T M-

    8 0 1 2 C- S L i G f r o m S o u r ce P h o t on i c s ( F i b e rx o n ) .

    M o du l e d e ta i ls : D a ta r a te 1 2 50 M b/ s , w a ve l en g th 8 5 0n m, m u lt i mo d e,

    t e mp e ra t ur e r a ng e - 4 0 C ~ + 8 5 C ( -4 0 F ~ 1 8 5 F )

    L C m o d u le d a t a

    8 8 - 13 2 VA C / 4 5 - 16 0 V DC

    1 76 - 26 4 VA C / 2 00 - 37 0 V DC

    R e d u nd a n t p o w e r s u p p ly i s o p t i o na l

    Power supply

    60W max.Power consumption

    60W max.H e a t p r o d uc t i o n

    438W x 130H x 312D mm (excluding rack mount accessories)

    3 U h e i g h t, 1 9 " r a c k m o u nt a b l e

    Dimension

    34

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    35/42

  • 7/23/2019 Abb - Sys600c

    36/42

  • 7/23/2019 Abb - Sys600c

    37/42

    C a pa c i ty a n d p e rf o r ma n ce7.

    S Y S 6 0 0C c ap a ci t y7.1.

    This chapter gives an overview of the capacity of SYS 600C regarding the following

    functions or aspects:

    Number of IEDs that can be connected

    Usage of the following functions: workplaces and process displays, gateway, mir-

    roring, HSB

    Data logging (for example, for measurement reports and trends) and event logging

    Conditions:

    The capacity information is only applicable, when no additional software is installed

    and/or running in the computer.

    The average CPU load of the computer must not exceed 50%.

    The system size capacity figures follow these principles:

    A guideline for the maximum process communication (Number of IEDs or Number

    of Messages/sec.) is given. This includes the process communication functions and

    the logging of data in the process database.

    If other functions are added, such as gateway or workplaces, they consume computer

    capacity and thereby the process communication capacity must be reduced accord-

    ingly. For IEC 61850 the capacity is mainly affecting the number of messages, and

    thus it is more important that this is reduced than the number of IEDs.

    The impact on the process communication capacity of the other functions is given

    in percentage.

    Example: How many IEDs can be connected over IEC 61850 to SYS 600C that acts as

    a gateway with one NCC connection and one operator workplace?

    Maximum of 160 IEDs can be connected over IEC 61850 (with 12 msg/s/IED), see

    Table7.3-1.

    The following functions are also needed:

    One NCC connection (-25%)

    1 workplace (-5%)

    The process communication capacity in this case is:

    75% * (95% * 160 IEDs) = 114 IEDs or

    75% * (95% * 1920 ) msg/s = 1368 msg/s

    D a ta l o g g in g c a p a c ity7.2.

    The data logging capacity concerns logging to disk and is limited by the available disk

    capacity. Roughly 1 GB of disk capacity is allocated for event logging and the same

    amount for data logging.

    37

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    38/42

    This corresponds to:

    Number of events: 3 000 000

    Number of logged values: 90 000 000

    The maximum number of logged values corresponds roughly to 400 measurements

    sampled every 15 minutes and stored for 1 + 5 years (current year + 5 years of history).

    P ro c es s c o m mu n i c ati o n c a pa c i ty7.3.

    The capacity of one protocol means that only that protocol is used. If several protocols

    are combined, the maximum capacity per protocol must be reduced proportionally.

    Example: IEC 61850 and LON are combined in the system. The IEC 61850 IEDs represent

    60% of the maximum IEC 61850 capacity. Then the actual maximum LON capacity is

    40% of the indicated maximum capacity.

    The following tables show the maximum communication capacity for the most commonly

    used protocols.

    T ab l e 7 . 3 -1 M a x im u m c o m mu n i ca t i on c a pa c i ty

    CommentsValueIEC 61850

    1920/sN r o f m e s sa g e s

    160N r o f I E Ds

    4N r of I E C 6 1 85 0 c l ie n ts

    LON

    M a x im u m 3 0 I E D s p e r XL O N c a r d90N r o f I E Ds

    L i mi t ed b y a v ai l ab l e P C I s l ot s3N r o f X L O N c a r d s

    IEC 103

    200N r o f I E Ds

    Limited mostly by maximum response

    time

    15N r o f I ED s / l in e

    IEC 101

    200N r o f I E Ds

    Limited mostly by maximum responsetime15N r o f I ED s / l in e

    IEC 104

    I f I / O c o un t i s sm a ll , n u mb e r o f I E Ds ca n

    b e b ig ge r

    200N r o f I E Ds

    15N r o f I ED s / l in e

    SPA

    200N r o f I E Ds

    38

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    39/42

    L i mi t ed m os t ly b y m a xi m um r e sp o ns etime

    15N r o f I ED s / l in e

    M o db u s R T U

    200N r o f I E Ds

    L i mi t ed m os t ly b y m a xi m um r e sp o ns e

    time

    15N r o f I ED s / l in e

    M o db u s T C P

    200N r o f I E Ds

    L i mi t ed m os t ly b y m a xi m um r e sp o ns e

    time

    15N r o f I ED s / l in e

    D N P s e ri a l

    200N r o f I E Ds

    L i mi t ed m os t ly b y m a xi m um r e sp o ns etime

    15N r o f I ED s / l in e

    D NP L AN

    I f I /O c ou nt i s s ma l l, n um be r o f I ED s c an

    b e b ig ge r

    200N r o f I E Ds

    15N r o f I ED s / l in e

    T ab l e 7 . 3 -2 I m p ac t o n p r o ce s s c o m mu n i ca t i on

    CommentsI m p a ct o n p r o c e ss c o m -

    munication

    Function

    Always included- 0%Local process database

    - 2%Mirroring

    - 2%H o t S t a n d- b y r e d u n d an c y

    - 2 5 % w he n t ot al d a ta u pd at e r at e t o a ll

    N C C s i s 5 0 % f r o m t h e p r o c es s d at a

    u p da t e r a te

    - 25 % - 0%G a t e wa y / N C C c o nn e c -

    tions

    - 2 4% w he n P ro ce ss d is pl ay w it h 1 0 50

    m e as u re m en t o b je c ts i n W or k pl a ce

    - 1 8% w he n P ro ce ss d is pl ay w it h 1 0 50

    s wi t ch i ng d e vi c e o b je c ts i n W or k pl a ce

    - 4 % w h en P r oc e ss d i sp l ay w i th 1 5 0m e as u re m en t o b je c ts i n W or k pl a ce

    - 2 % w h en P r oc e ss d i sp l ay w i th 1 5 0

    s wi t ch i ng d e vi c e o b je c ts i n W or k pl a ce

    - 24 % - 1%Process display Work-

    place

    P e r W or k pl a ce w i th T re n ds w i th 1 0c u rv e s o n 3 0 s e co n ds i n t e rv a l l o gg i ng

    - 1%T r en d s W o r k p l ac e w i t hd a ta l o gg i ng

    39

    S YS 6 00 C 1. 93MicroSCADA Pro1MRS757258

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    40/42

    CommentsI m p a ct o n p r o c e s s c o m -

    munication

    Function

    P e r Wo r k pl a c e w i t h M e a su r e me n t

    R e po r ts w i th 1 5 m i n r e po r t

    To t al o f 9 0 0 o b je c ts d a ta l o gg e d b y

    M e a su r e m en t R e p o rt s

    - 1%R e p o rt s W o r k p ac e w i t h

    d a ta l o gg i ng

    The following list shows some examples when IEDs are connected to SYS 600C with

    the following Gateway or NCC connections and with Local process database:

    NCC connection with one DNP LAN communication including 84 IEDs resulting

    in 1 000 process updates per second sent to one NCC*)

    NCC connection with two DNP LAN communications including 67 IEDs resulting

    in 1 600 process updates per second sent to two NCCs*)

    NCC connection with one IEC 104 LAN communication including 158 IEDs resultingin 1 900 process updates per second sent to one NCC

    NCC connection with two IEC 104 LAN communications including 116 IEDs res-

    ulting in 2 800 process updates per second sent to two NCCs

    *)90% 16-bit analog data without time, 5% binary data without time and 5% binary data

    with time

    The following list shows some examples when IEDs are connected to SYS 600C with

    Local process database and displayed with Workplaces:

    60 IEDs with IEC 61850 protocol and 1 Workplace with 1 050 display objects

    63 IEDs with IEC 61850 protocol and 2 Workplaces both including 450 displayobjects

    77 IEDs with IEC 61850 protocol and 1 Workplace including 150 display objects

    40

    1MRS757258MicroSCADA ProS YS 6 00 C 1. 93

    P r o du c t G u i de

  • 7/23/2019 Abb - Sys600c

    41/42

  • 7/23/2019 Abb - Sys600c

    42/42

    C on ta ct u s

    1MRS757258A/30.6

    .2010

    Copyright2010ABB.Allrightsreserved.

    ABB Oy

    Substation Automation Pr oducts

    P. O. B ox 6 99

    F I - 6 51 0 1 VA A S A, F I N L AN D

    Tel. +358 10 22 11

    Fax. +358 10 224 1094

    www.abb.com/substationautomation